FAIL (the browser should render some flash content, not this).


Application . . .

Process Temperature Maintenance or Freeze Protection
High performance VSX self-regulating heating cables are designed specifically for process temperature maintenance or freeze protection where high maintain temperatures or high temperature exposure are required.

The heat output of VSX cable varies in response to the surrounding temperature by reducing its thermal output with increasing temperature. With its high self-regulating characteristic, VSX can be installed in hazardous areas requiring a T3 temperature class rating.

VSX cables are approved for use in ordinary (non-classified) areas, Division 2 classified areas, and Zone 1 and 2 Classified areas.

Ratings . . .

Available watt densities ............. 5, 10, 15, 20 w/ft @ 50°F
...................................................(16, 33, 49, 66 w/m @ 10°C)
Supply voltages ........................ 110 - 120 or 208 - 277 VAC
Max. maintenance temperature ................... 300°F (149°C)
Max. intermittent exposure temperature
__ Power-on ..................................................
450°F (232°C)
Minimum installation temperature ............... - 60°F (- 51°C)
Minimum bend radius .................................... 1.25" (32 mm)
T-rating¹ .................................................... T3 392°F (200°C)

 

Notes . . .

1. T-rating per the 1996 NEC, Tables 500-3(d), 505-10(b) and as verified by Factory Mutual Research and the Canadian Standards Association.